Description
The Schneider Electric TeSys Deca GV2ME14 is a reliable 3-pole motor circuit breaker designed for 3-phase motor applications ranging from 3 to 4 kW at 400V. Featuring a thermal setting range of 6–10A and magnetic tripping at 13×In, it ensures effective thermal-magnetic protection against overloads and short circuits. With a high breaking capacity of 100kA at 400V, it guarantees operational safety in demanding environments. The unit supports screw clamp terminal connections and start-stop control via push-buttons, tested for up to 100,000 AC-3 cycles. Certified to multiple global standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX) and Green Premium compliant, this breaker is suitable for industrial, marine, and hazardous applications.
Specifications
| Feature | Details |
|---|---|
| Product Model | GV2ME14 |
| Type | Motor Circuit Breaker |
| Poles | 3P |
| Thermal Setting Range | 6–10A |
| Magnetic Tripping | 13 × In |
| Rated Operational Voltage | 690V |
| Motor Rating | 3–4 kW @ 400V |
| Breaking Capacity (Icu) | 100kA @ 400V |
| Control Type | Push-button (Start/Stop) |
| Connection Type | Screw clamp terminals |
| Endurance | 100,000 cycles (AC-3) |
| Certifications | IEC, UL, CSA, CCC, EAC, Marine, ATEX |
| Compliance | RoHS / REACh (Green Premium) |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 78.5 mm |
| Net Weight | 0.26 kg |







There are no reviews yet.